Overview
- Versatile analog input module designed for industrial automation
- Provides 16 independently configured analog input channels
- Suitable for monitoring thermocouples, RTDs, millivolts, and current measurements
Technical Specifications
Power Requirements
- Operating Voltage: 5 VDC at 500 mA typical, maximum 750 mA
- Overvoltage Category (IEC 61010-1): I for circuit above 150V, II for circuit below 150V
Analog Input Channels
- Thermocouples: Type B, E, J, K, L, N (14 AWG), N (28 AWG), R, S, T, U, Chinese type E and Chinese type S
- Resistance Temperature Detectors (RTDs): 100 Ω platinum (U.S. Lab. Standard, U.S. Industry Standard, European Standard), 120 Ω nickel, 10 Ω copper, Chinese 53 Ω copper
- Millivolt: -100 mV to +100 mV, 0 to 100 mV
- Voltage: 1 to 5 VDC, 0 to 5 VDC, 0 to 10 VDC, -10 VDC to +10 VDC, or user-specified range within -10 VDC and +10 VDC
- Current: 4 to 20 mA, system or external power
Input Impedance
- Current: 10 MΩ minimum (mV, TC)
- Voltage: 100 kΩ minimum (V, mA)
A-to-D Resolution
- Conversion: 24 bits
- Time: 180 msec for all 16 channels (each channel has dedicated A/D converter)
Accuracy
- Current: 0.02% of full scale range
- High Level Voltage: 0.04% of full scale range
- Low Level Voltage: 0.03% of full scale range
- Resistance: 0.05% of full scale range
- Temperature Effect (0° to 70° C): ± 0.003% of full scale range per degree C maximum
Maximum Lead Wire Resistance Effect
-
Voltage:
- Uncompensated: 1 µV of error per Ω of lead wire resistance
- Compensated: 0.1 µV of error per Ω of lead wire resistance
-
Resistance:
- Uncompensated: 0.020 Ω error per Ω of lead wire resistance
- Compensated: 0.008 Ω of error per Ω of lead wire resistance
Input Setting (Time)
- 1.5 seconds to within 1% after full scale step change
Cold Junction Reference Accuracy
- ± 0.5° C
Software Temperature Linearization Accuracy
- ± 0.1° C
Common Mode Isolation
- Channel to Channel and Channel to Logic: 250 VDC/VRMS at 60 Hz
-
Rejection (50-60 Hz):
- Normal Mode: -80 dB minimum
- Common Mode: -120 dB minimum
- Peak or Continuous Voltage: ± 15 VDC absolute maximum
Electromagnetic Compatibility
-
Conducted Transients:
-
Electrostatic Discharge (IEC 61000-4-2, EN 61000-4-2):
- Contact: ±6 kV
- Air: ±8 kV
- Insulation Resistance (100/500 VDC): 100 MΩ N/A
- Dielectric VAC (45 - 65 Hz) or VDC: 1.4 kV rms/1min. or 1.95 kV DC/1min.
- Impulse Voltage (1.2/50 µS): ±2.55 kVp ±1 kVp
- Voltage/Current Surge (1.2/50 µS to 8/20 µS) (IEC 61000-4-5, EN 61000-4-5): ±2 kVP ±1 kVP
- Fast Transient Bursts (IEC 61000-4-4, EN 61000-4-4): ±2 kVP N/A
- Damped Oscillatory Wave, 0.1 MHz and 1 MHz (IEC 61000-4-12, EN 61000-4-12): ±1 kVP ±0.5 kVP
- Ring Wave (IEC 61000-4-12, EN 61000-4-12): ±2 kVP ±1 kVP
-
Electrostatic Discharge (IEC 61000-4-2, EN 61000-4-2):
Montre plus
Quantité minimale de commande (MOQ)
Nous acceptons les commandes groupées et avons une quantité minimale de commande d’une seule unité.
Certificats et documentation
Sur demande, nous pouvons fournir tous les documents nécessaires, y compris les certificats d'origine/conformité et autres documents d'exportation requis.
Délai de livraison
Pour les articles en stock, notre objectif est de livrer dans un délai de 1 à 3 jours après confirmation du paiement. Les articles avec des délais de livraison spécifiés seront livrés selon le calendrier indiqué.
méthodes de payement
Nous acceptons le paiement 100% T/T (transfert télégraphique) avant l'expédition. Pour les articles avec des délais de livraison, un acompte de 30 % est requis à l’avance, les 70 % restants étant dus avant expédition. Pour les transferts en RMB, veuillez nous contacter si vous avez un agent en Chine.
garantie
Nous offrons une garantie standard d'un an sur tous les articles neufs et originaux. Si vous avez besoin d'une garantie prolongée, veuillez nous contacter pour plus de détails sur les coûts supplémentaires.
Politique de remboursement et de retour
Votre satisfaction est importante pour nous. Si vous devez retourner un article, cela doit être fait dans les 30 jours suivant la date de commande. Le produit doit être inutilisé, non ouvert et dans son emballage d'origine avec tous les accessoires inclus. Les remboursements sont traités dans les 5 à 7 jours ouvrables après réception de l'article retourné. Veuillez noter que les frais d'expédition et connexes ne sont pas remboursables.