Skip to content
Yokogawa AAP135-S00 Pulse Input Module

Yokogawa AAP135-S00 Pulse Input Module

  • 1000 In stock
  • Manufacturer: Yokogawa

  • Product No.: AAP135-S00

  • Condition: In stock

  • Product Type: Pulse Input Module

  • Product Origin: Japan

  • Payment:T/T, Western Union

  • Weight: 300g

  • Shipping port: Xiamen

  • Warranty: 12 months

{"id":41599706267738,"title":"Default Title","option1":"Default Title","option2":null,"option3":null,"sku":"AAP135-S00","requires_shipping":true,"taxable":true,"featured_image":null,"available":true,"name":"Yokogawa AAP135-S00 Pulse Input Module","public_title":null,"options":["Default Title"],"price":15800,"weight":300,"compare_at_price":21500,"inventory_management":"shopify","barcode":"Japan","requires_selling_plan":false,"selling_plan_allocations":[]}

Description

Overview

The Yokogawa AAP135-S00 is a pulse input module designed for use within Yokogawa's CENTUM CS3000 distributed control system (DCS). It processes pulse signals from field devices like flow meters and counters.

Key Features and Functions

  • Purpose: Receives and processes pulse signals from field devices in a Yokogawa DCS.
  • Input Types: Supports various pulse signal types, including:
    • Contact ON/OFF (dry contact)
    • Voltage pulse
    • Current pulse

Signal Processing and Isolation

  • Isolation: The module provides isolation between:
    • Field inputs and the system
    • Individual channels This design protects against electrical noise and faults in field wiring.

Channels and Frequency Range

  • Channels: Typically features 8 isolated input channels.
  • Frequency Range: Handles pulse frequencies up to 10 kHz.

Redundancy and Applications

  • Redundancy: Supports dual-redundant configurations for greater system reliability.
  • Applications: Widely used in industries such as:
    • Oil and gas
    • Chemical processing
    • Power generation
    • Water and wastewater treatment

Detailed Specifications

  • Input Signal Types:
    • 2-wire type: Contact ON/OFF, voltage pulse, current pulse (possible to supply transmitter power).
    • 3-wire type: Power-supply-type voltage pulse.
  • Input Frequency: From 0 to 10 kHz.

Withstanding Voltage

  • Input to system: 500 V AC for 1 minute.
  • Between channels: 500 V AC for 1 minute.

Pulse Input Characteristics

  • Minimum Input Pulse Width: 40 µs.
  • Input Signal Level:
    • Contact input: Open/close levels for relay or transistor contact.
    • Open: 100 kΩ or larger.
    • Close: 200 Ω or less.

Contact Capacity

  • 12 V DC: 15 V DC, 15 mA or higher.
  • 24 V DC: 30 V DC, 30 mA or higher.

Voltage/Current Pulse Input

  • High Level (VH): 3 to 24 V DC.
  • Low Level (VL): -1 to 8 V DC.
  • Swing Value: 3 V or higher.

Features

We welcome bulk orders and have a minimum order quantity of just one unit.

Upon request, we can provide all necessary documentation, including Certificates of Origin/Conformance and other required export documents.

For items in stock, we aim to deliver within 1-3 days after payment confirmation. Items with specified lead times will be delivered according to the quoted schedule.

We accept 100% T/T (Telegraphic Transfer) payment before shipping. For items with lead times, a 30% deposit is required upfront, with the remaining 70% due before shipment. For RMB transfers, please contact us if you have an agent in China.

We offer a standard one-year warranty on all new and original items. If you require an extended warranty, please contact us for additional cost details.

Your satisfaction is important to us. If you need to return an item, it must be done within 30 days of the order date. The product must be unused, unopened, and in its original packaging with all accessories included. Refunds are processed within 5-7 business days after we receive the returned item. Please note that shipping and related charges are non-refundable.

Featured