YOKOGAWA S2BN1D-19030 S2 Terminal Base Plate

YOKOGAWA S2BN1D-19030 S2 Terminal Base Plate

  • 1000 In stock
  • Manufacturer: Yokogawa

  • Product No.: S2BN1D-19030

  • Condition: In stock

  • Product Type: S2 Terminal Base Plate

  • Product Origin: Japan

  • Payment:T/T, Western Union

  • Weight: 2000g

  • Shipping port: Xiamen

  • Warranty: 12 months

{"id":41515261263962,"title":"Default Title","option1":"Default Title","option2":null,"option3":null,"sku":"S2BN1D-19030","requires_shipping":true,"taxable":true,"featured_image":null,"available":true,"name":"YOKOGAWA S2BN1D-19030 S2 Terminal Base Plate","public_title":null,"options":["Default Title"],"price":33000,"weight":2000,"compare_at_price":63000,"inventory_management":"shopify","barcode":"Japan","requires_selling_plan":false,"selling_plan_allocations":[]}

Description

Overview

The Yokogawa S2BN1D-19030 terminal base plate is part of Yokogawa's ProSafe-RS safety instrumented system, designed to connect field devices to the system’s N-IO I/O unit. It supports both redundant and single configurations, providing 16 channels for flexible and reliable field signal connections. This unit is engineered for safety-critical applications, offering secure mounting options and robust electrical characteristics.

Technical Specifications

  • Mounting Options:

    • DIN Rail Mount Type: Standard for secure mounting on DIN rails.
    • Wall Mount Type: Mounted using M4 × 4 screws for stability.
  • I/O Module Configuration:

    • Supports Redundant or Single I/O configurations.
    • Provides 16 I/O channels for varied signal processing.
  • Connection Types:

    • Field Signal:
      • Pressure Clamp Terminal: (S2BN1D-1)
      • Spring Clamp Terminal: (S2BN1D-2)
      • Cable Connector: (S2BN1D-9)
    • F-SB Bus: Connect via F-SB Bus Cable (S2KLF10).
    • System Power Supply: Use Power Supply Cable for Base Plate (S2KPB10).
  • Grounding: Ground connection via M3 screw terminal.

  • Electrical and Safety Ratings:

    • Withstanding Voltage:
      • Between input/output and system: 1500 V AC for 1 minute.
      • Continuous 42 V DC.
    • Insulation Resistance: 100 MΩ or more at 500 V DC.
  • Weight: Approximately 1.4 kg.

  • Field Power Supply:

    • Rating: 24 V DC, with a tolerance of +20%/-10%, up to 11.0 A.
    • Connection: Connected via cable to the field power supply terminal (EP+, EP-).
  • Over Voltage Protection (OVP): Detection level at 32 V or lower.

  • Withstanding Voltage to Ground: 500 V AC or higher for 1 minute.

  • Capacitance: Between output and ground is 0.4 μF or less.

Features

We welcome bulk orders and have a minimum order quantity of just one unit.

Upon request, we can provide all necessary documentation, including Certificates of Origin/Conformance and other required export documents.

For items in stock, we aim to deliver within 1-3 days after payment confirmation. Items with specified lead times will be delivered according to the quoted schedule.

We accept 100% T/T (Telegraphic Transfer) payment before shipping. For items with lead times, a 30% deposit is required upfront, with the remaining 70% due before shipment. For RMB transfers, please contact us if you have an agent in China.

We offer a standard one-year warranty on all new and original items. If you require an extended warranty, please contact us for additional cost details.

Your satisfaction is important to us. If you need to return an item, it must be done within 30 days of the order date. The product must be unused, unopened, and in its original packaging with all accessories included. Refunds are processed within 5-7 business days after we receive the returned item. Please note that shipping and related charges are non-refundable.

Featured

Complementary products